Connection or frame of the communication for 4110 configuration and state is invalid true 0 4110 communication failed
The connection for configuration and state to 4110 was broken or the frame is not correct
Causes related to the alarm
Timestamp update error (TIME) Data block header, footer or length mismatch (FERROR) Data block version mismatch (FVERS) Data block alive counter update error (ALIVEC) Frame lost due (FLOST) PLC communication broken (CFGSTAT) Lost a redundant CPU (CPU0-ALIVE, CPU1-ALIVE)
Corrective action
Check whether the PLC is running\n Check whether network is ok\n Contact maintenance service (if needed)
4110 State Comm. Alarm OPI
/opt/codac/opi/boy/resources/alarmpages/healthMonitoring/ITER-SYSM-PLCHLTS_Alarm.opi "CBS1=EC, CBS2=GN, PP=01, NNNN=4110, TTT=PLC, PPPP=52RF, ALARM_PV=EC-GN-SYSM-52RF-01:PLC4110-PLCHLTS, ALARM_PATH=/CODAC_AlarmHandler/EC/EC-GN/EC-GN-SYSM, LEVEL=ITER-EC-GN-SYSM, ALARM_GUIDANCE1_TITLE=PLC communication failed, ALARM_GUIDANCE1_DETAILS=The connection for configuration and state to PLC is broken or the frame is not correct."
Connection or frame of the communication for PLC Event is invalid true 0 PLC Event communication failed
The connection for event to PLC was broken or the frame is not correct
Causes related to the alarm
Event Frame count update error (FRAMEC) PLC Event communication broken (EVTSTAT)
Corrective action
Check whether the PLC is running\n Check whether network is ok\n Contact maintenance service (if needed)
PLC Event Comm. Alarm OPI
/opt/codac/opi/boy/resources/alarmpages/healthMonitoring/ITER-SYSM-EVTHLTS_Alarm.opi "CBS1=EC, CBS2=GN, CBS3=SYSM, PP=01, NNNN=4110, TTT=PLC, PPPP=52RF, ALARM_PV=EC-GN-SYSM-52RF-01:PLC4110-EVTHLTS, ALARM_PATH=/CODAC_AlarmHandler/EC/EC-GN/EC-GN-SYSM, LEVEL=ITER-EC-GN-SYSM, ALARM_GUIDANCE1_TITLE=PLC Event communication failed, ALARM_GUIDANCE1_DETAILS=The connection for event to PLC was broken or the frame is not correct."
Any one of CPU, MEM, Disk, FD, Process of the host is in alarm state true 0 System is an abnormal state
Check the mentioned alarm load and identify the cause
System resources related to the alarm
1 - one of CPU, Disk, Memory, FD load is high or necessary process has been stopped 2 - two of CPU, Disk, Memory, FD load are high and/or necessary process has been stopped 3 - three of CPU, Disk, Memory, FD load are high and/or necessary process has been stopped
Corrective action
If any load remains high continuously, contact maintenance service. In addition, check if the necessary processes are running
Temporary actions to suppress
Change the alarm limits or severity for each load in alarm state. Ex1) alarm limits % caput EC-GN-SYSM-52RF-01:PCF4210-CPUUTL.HIGH 90 % caput EC-GN-SYSM-52RF-01:PCF4210-CPUUTL.HIHI 100 Ex2) alarm severity % caput EC-GN-SYSM-52RF-01:PCF4210-MEMUTL.HSV NO_ALARM % caput EC-GN-SYSM-52RF-01:PCF4210-MEMUTL.HHSV NO_ALARM
System Health Alarm OPI
/opt/codac/opi/boy/resources/alarmpages/healthMonitoring/ITER-SYSM-SHLT_Alarm.opi "CBS=EC-GN-SYSM, PPPP=52RF, PP=01, TTT=PCF, NNNN=4210, ALARM_PV=EC-GN-SYSM-52RF-01:PCF4210-SHLT, ALARM_PATH=/CODAC_AlarmHandler/EC/EC-GN/EC-GN-SYSM, LEVEL=ITER-EC-GN-SYSM, ALARM_GUIDANCE1_TITLE=System resource utilization is high, ALARM_GUIDANCE1_DETAILS=Any one of CPU / MEM / Disk / FD / Process of the host is in alarm state. Check the mentioned alarm load and identify the cause. If any load remains high continuously contact maintenance service."
Any one of CPU, MEM, Disk or FD of the host is in alarm state true 0 System resource utilization is high
Check the mentioned alarm load and identify the cause
System resources related to the alarm
1 - CPU utilization high (CPUUTL) : CPU utilization is high 2 - Memory utilization high (MEMUTL) : Memory utilization is high 3 - CPU, Mem util high (CPUUTL, MEMUTL) : CPU and Memory utilizations are high 4 - Disk utilization high (DISKUTL) : Disk utilizations are high 5 - CPU, Disk util high (CPUUTL,DISKUTL) : CPU and Disk utilizations are high 6 - Mem, Disk util high (MEMUTL,DISKUTL) : Memory and Disk utilizations are high 7 - CPU, Mem, Disk util high (CPUUTL,MEMUTL,DISKUTL) : CPU/Memory/Disk utilizations are high 8 - FD utilization high (FDUTL) : FD utilization is high 9 - CPU, FD util high (CPUUTL,FDUTL) : CPU and FD are in alarm state 10 - Mem, FD util high (MEMUTL,FDUTL) : Memory and FD are in alarm state 11 - CPU, Mem, FD alarm (CPUUTL,MEMUTL,FDUTL) : CPU/Memory/FD are in alarm state 12 - Disk, FD util high (DISKUTL,FDUTL) : Disk and FD are in alarm state 13 - CPU, Disk, FD alarm (CPUUTL,DISKUTL,FDUTL) : CPU/Disk/FD are in alarm state 14 - Mem, Disk, FD alarm (MEMUTL,DISKUTL,FDUTL) : Memory/Disk/FD are in alarm state 15 - CPU,Mem,Disk,FD alarm (CPUUTL,MEMUTL,DISKUTL,FDUTL) : CPU/Memory/Disk/FD alarm
Corrective action
If any load remains high continuously, contact maintenance service
Temporary actions to suppress
Change the alarm limits or severity for each load in alarm state. Ex1) alarm limits % caput EC-GN-SYSM-52RF-01:PCF4210-CPUUTL.HIGH 90 % caput EC-GN-SYSM-52RF-01:PCF4210-CPUUTL.HIHI 100 Ex2) alarm severity % caput EC-GN-SYSM-52RF-01:PCF4210-MEMUTL.HSV NO_ALARM % caput EC-GN-SYSM-52RF-01:PCF4210-MEMUTL.HHSV NO_ALARM
System Health Alarm OPI
/opt/codac/opi/boy/resources/alarmpages/healthMonitoring/ITER-SYSM-SYSHLTS_Alarm.opi "CBS=EC-GN-SYSM, PPPP=52RF, PP=01, TTT=PCF, NNNN=4210, ALARM_PV=EC-GN-SYSM-52RF-01:PCF4210-SYSHLTS, ALARM_PATH=/CODAC_AlarmHandler/EC/EC-GN/EC-GN-SYSM, LEVEL=ITER-EC-GN-SYSM, ALARM_GUIDANCE1_TITLE=System resource utilization is high, ALARM_GUIDANCE1_DETAILS=Any one of CPU / MEM / Disk / FD of the host is in alarm state. Check the mentioned alarm load and identify the cause. If any load remains high continuously contact maintenance service."
Current state of TCNd and the synchronization state of the device true 0 System time synchronization is not fully operational
If status is N/A, then check that tcnd is running. If status is not operational for some time, please contact maintenance service.
Documentation TCNd
firefox file:///opt/codac/doc/pdf/TCNd_User_Manual.pdf
TCNd Sync. Alarm OPI
/opt/codac/opi/boy/resources/alarmpages/healthMonitoring/ITER-SYSM-TSTATUS_Alarm.opi "CBS=EC-GN-SYSM, PPPP=52RF, PP=01, TTT=PCF, NNNN=4210, ALARM_PV=EC-GN-SYSM-52RF-01:PCF4210-TSTATUS, ALARM_PATH=/CODAC_AlarmHandler/EC/EC-GN/EC-GN-SYSM, LEVEL=ITER-EC-GN-SYSM, ALARM_GUIDANCE1_TITLE=System clock synchronization with respect to ITER time, ALARM_GUIDANCE1_DETAILS=The computer system clock is synchronized to ITER time using the TCN daemon (TCNd) component of CODAC Core SYstem. Please see TCNd User Manual (ITER_D_MUYNT6 - /opt/codac/doc/pdf/TCNd_User_Manual.pdf). The clock synchronization has been detected to have been in an abnormal state. i.e. STATUS different from 'Operational' after two minutes of uptime."
Any one of CPU, MEM, Disk, FD, Process of the host is in alarm state true 0 System is an abnormal state
Check the mentioned alarm load and identify the cause
System resources related to the alarm
1 - one of CPU, Disk, Memory, FD load is high or necessary process has been stopped 2 - two of CPU, Disk, Memory, FD load are high and/or necessary process has been stopped 3 - three of CPU, Disk, Memory, FD load are high and/or necessary process has been stopped
Corrective action
If any load remains high continuously, contact maintenance service. In addition, check if the necessary processes are running
Temporary actions to suppress
Change the alarm limits or severity for each load in alarm state. Ex1) alarm limits % caput EC-GN-SYSM-52RF-01:PSH4410-CPUUTL.HIGH 90 % caput EC-GN-SYSM-52RF-01:PSH4410-CPUUTL.HIHI 100 Ex2) alarm severity % caput EC-GN-SYSM-52RF-01:PSH4410-MEMUTL.HSV NO_ALARM % caput EC-GN-SYSM-52RF-01:PSH4410-MEMUTL.HHSV NO_ALARM
System Health Alarm OPI
/opt/codac/opi/boy/resources/alarmpages/healthMonitoring/ITER-SYSM-SHLT_Alarm.opi "CBS=EC-GN-SYSM, PPPP=52RF, PP=01, TTT=PSH, NNNN=4410, ALARM_PV=EC-GN-SYSM-52RF-01:PSH4410-SHLT, ALARM_PATH=/CODAC_AlarmHandler/EC/EC-GN/EC-GN-SYSM, LEVEL=ITER-EC-GN-SYSM, ALARM_GUIDANCE1_TITLE=System resource utilization is high, ALARM_GUIDANCE1_DETAILS=Any one of CPU / MEM / Disk / FD / Process of the host is in alarm state. Check the mentioned alarm load and identify the cause. If any load remains high continuously contact maintenance service."
Any one of CPU, MEM, Disk or FD of the host is in alarm state true 0 System resource utilization is high
Check the mentioned alarm load and identify the cause
System resources related to the alarm
1 - CPU utilization high (CPUUTL) : CPU utilization is high 2 - Memory utilization high (MEMUTL) : Memory utilization is high 3 - CPU, Mem util high (CPUUTL, MEMUTL) : CPU and Memory utilizations are high 4 - Disk utilization high (DISKUTL) : Disk utilizations are high 5 - CPU, Disk util high (CPUUTL,DISKUTL) : CPU and Disk utilizations are high 6 - Mem, Disk util high (MEMUTL,DISKUTL) : Memory and Disk utilizations are high 7 - CPU, Mem, Disk util high (CPUUTL,MEMUTL,DISKUTL) : CPU/Memory/Disk utilizations are high 8 - FD utilization high (FDUTL) : FD utilization is high 9 - CPU, FD util high (CPUUTL,FDUTL) : CPU and FD are in alarm state 10 - Mem, FD util high (MEMUTL,FDUTL) : Memory and FD are in alarm state 11 - CPU, Mem, FD alarm (CPUUTL,MEMUTL,FDUTL) : CPU/Memory/FD are in alarm state 12 - Disk, FD util high (DISKUTL,FDUTL) : Disk and FD are in alarm state 13 - CPU, Disk, FD alarm (CPUUTL,DISKUTL,FDUTL) : CPU/Disk/FD are in alarm state 14 - Mem, Disk, FD alarm (MEMUTL,DISKUTL,FDUTL) : Memory/Disk/FD are in alarm state 15 - CPU,Mem,Disk,FD alarm (CPUUTL,MEMUTL,DISKUTL,FDUTL) : CPU/Memory/Disk/FD alarm
Corrective action
If any load remains high continuously, contact maintenance service
Temporary actions to suppress
Change the alarm limits or severity for each load in alarm state. Ex1) alarm limits % caput EC-GN-SYSM-52RF-01:PSH4410-CPUUTL.HIGH 90 % caput EC-GN-SYSM-52RF-01:PSH4410-CPUUTL.HIHI 100 Ex2) alarm severity % caput EC-GN-SYSM-52RF-01:PSH4410-MEMUTL.HSV NO_ALARM % caput EC-GN-SYSM-52RF-01:PSH4410-MEMUTL.HHSV NO_ALARM
System Health Alarm OPI
/opt/codac/opi/boy/resources/alarmpages/healthMonitoring/ITER-SYSM-SYSHLTS_Alarm.opi "CBS=EC-GN-SYSM, PPPP=52RF, PP=01, TTT=PSH, NNNN=4410, ALARM_PV=EC-GN-SYSM-52RF-01:PSH4410-SYSHLTS, ALARM_PATH=/CODAC_AlarmHandler/EC/EC-GN/EC-GN-SYSM, LEVEL=ITER-EC-GN-SYSM, ALARM_GUIDANCE1_TITLE=System resource utilization is high, ALARM_GUIDANCE1_DETAILS=Any one of CPU / MEM / Disk / FD of the host is in alarm state. Check the mentioned alarm load and identify the cause. If any load remains high continuously contact maintenance service."